The K3128 is a 12kV High Voltage Digital Insulation Tester with 6 ranges, 500, 1000, 2500, 5000, 10000 and 12000V with a fine adjustment setting (5V to 100V steps) with an insulation resistance up to 35TΩ. The microprocessor controlled K3128 is ideal for analyzing the insulation characteristics of cables, transformers, motors, generators, high pressure switches, insulators and large wiring installations. It is housed in robust IP64 (lid closed) case, ideal for extended field usage, powered by rechargeable batteries and an AC input which can be operated while under charge. After a completion of an insulation test, the K3128 automatic discharge and display the test voltage. Data storage of test is available in 3 types of data: logging Data (REC File), Measured Data (Save File), and Print Screen (BMP File), this captures and saves the screen images.
Insulation Testers
12kV High Voltage Digital Insulation Tester
Availability:
Out of stock
R159,850.00
- Insulation Resistance (IR) & Leak Current with a wide range of measurement from 500V-1000V-2500V-5000V-10000V-12000V
- Insulation resistance up to 35TΩ
- Variable test voltage of 5V to 100V steps
- Voltage & elapsed time are displayed
- Polarization Index (PI)
- Dielectric Absorption Ratio (DAR)
- Step Voltage (SV)
- Dielectric Discharge Index (DD)
- Capacitance measurement
- Auto discharge function and voltage output warning function
- Internal Memory– max 40,000 data
- Built-in Print Screen Function enables to record display screen, records 32 screens max
- Downloading to PC – using the USB cord and the PC software included as standard accessories, the memory data or the measuring data can be transmitted to a PC at real time
- Mains and battery powered – internal battery can be charged during normal operation
- Robust design for field use with weatherproof protection in IP64 casing with lid closed
- Large backlit LCD graphic display with bargraph
Out of stock
Request a quote
12kV High Voltage Digital Insulation Tester
R159,850.00Specifications
Function | Range | Resolution | Accuracy |
DC voltage | 30v – 600V | 1V | ± (2.0% + 3 Digits) |
AC voltage | 30v – 600V | 1V | ± (2.0% + 3 Digits) |
Insulation resistance 250V | 250V | 0.0 – 100.0MΩ | |
Insulation resistance 500V | 500V | 0.0 – 1000MΩ | ± (5.0% + 3 Digits) |
Insulation resistance 1000V | 1000V | 0.0 – 2.00GΩ | ± (5.0% + 3 Digits) |
Insulation resistance 2500V | 2500V | 0.0 – 100.0GΩ | ± (5.0% + 3 Digits) |
Insulation resistance 5000V | 5000V | 0.0 – 1000GΩ | ± (5.0% + 3 Digits) |
Capacitance measurement | 5.0nF – 50.0μF | ± (5.0% + 5 Digits) | |
Short circuit current | 1.5mA | ||
Current measurement Range | ± (10%) | ||
Overrange indication | Yes | ||
AC Bandwidth | 50.0Hz to 60.0Hz | ||
Digital Display | Large Graphical Display | ||
Polarization index | Yes | ||
Dielectric absorption ratio | Yes | ||
Auto discharge | Yes | ||
Bargraph | Yes | ||
Back Light | Yes | ||
Enclosure | Robust moulded case | ||
Low battery indication | Yes | ||
Power source | 8 x LR14 | ||
Weight | 1.9kG | ||
Dimensions | 177 x 226 x 100mm | ||
Safety Specs | IEC61010-1 CatIV 300V |